Yokogawa 202 Field Mounting Rate Totalizer Manual do Utilizador Página 15

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 34
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 14
Step Comment
CAL 11
Low Alarm - digits after the decimal point.
CAL 10 & 11 program the flowrate below which the
low alarm relay will close. The value can be
programmed in the range 0 to 999,999.
CAL 12
High Alarm or Pulse Output Factor - whole numbers.
CAL 13
High Alarm or Pulse Output Factor - digits after the
decimal point.
CAL 12 & 13 program the flowrate above which the
high alarm relay will close. The value can be
programmed in the range 0 to 999,999.
If the pulse output is selected (see CAL 00), the value will
represent the total per pulse. eg. 5 litres per pulse.
CAL 14
Input Flow Relationship.
0 = Linear Input
1 = Square Root Input.
CAL 15
Accumulated Total Reset.
CAL 15 displays the accumulated total which can be
reset by pressing and holding the RESET key for about
5 seconds.
SOFT
Software Version.
Programming 13
Vista de página 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 33 34

Comentários a estes Manuais

Sem comentários