Yokogawa YFGW610 Manual do Utilizador Página 31

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 45
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 30
<B4. Power, ground, and signal cable connection>
B4-5
IM 01W02D02-01EN
Table B4-1 List of power supply cables
Cable Dimensions (mm)
Phoenix Contact's
type
Section
area
(mm
2
)
AWG
Strip
length
(mm)
I
1
I
2
d
1
S
1
d
2
S
2
0.25 24 10 10.5 6.0 0.8 0.15 2.0 0.25 AI 0.25-6 BU
0.34 22
10 10.5 6.0 0.8 0.15 2.0 0.25 AI 0.34-6 TQ
10 12.5 8.0 0.8 0.15 2.0 0.25 AI 0.34-8 TQ
0.5 20
10 12.0 6.0 1.1 0.15 2.5 0.25 AI 0.5-6 WH
10 14.0 8.0 1.1 0.15 2.5 0.25 AI 0.5-8 WH
10 16.0 10.0 1.1 0.15 2.5 0.25 AI 0.5-10 WH
0.75 20
10 12.0 6.0 1.3 0.15 2.8 0.25 AI 0.75-6 GY
10 14.0 8.0 1.3 0.15 2.8 0.25 AI 0.75-8 GY
10 16.0 10.0 1.3 0.15 2.8 0.25 AI 0.75-10 GY
1.0 18
10 12.0 6.0 1.5 0.15 3.0 0.3 AI 1-6 RD
10 14.0 8.0 1.5 0.15 3.0 0.3 AI 1-8 RD
10 16.0 10.0 1.5 0.15 3.0 0.3 AI 1-10 RD
1.5 16
10 12.0 6.0 1.8 0.15 3.4 0.3 AI 1.5-6 BK
10 14.0 8.0 1.8 0.15 3.4 0.3 AI 1.5-8 BK
10 18.0 10.0 1.8 0.15 3.4 0.3 AI 1.5-10 BK
2.5 14
10 14.0 8.0 2.3 0.15 4.2 0.3 AI 2.5-8 BU
10 16.0 10.0 2.3 0.15 4.2 0.3 AI 2.5-10 BU
IMPORTANT
Use the same manufacturer for sleeves and tools.
Use sleeve tools that match the wire thickness.
Insert the wire to be connected completely into the pressure clamp terminal and attach it
securely.
Secure the cable to cable clamps, etc. so that the weight of the cable applied to the terminal
is minimized.
Vista de página 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 44 45

Comentários a estes Manuais

Sem comentários