2. HART COMMUNICATOR OPERATION
6
F0231.EPS
Because the reading on the
ammeter is 4.000 mA, select YES
and press ENTER (F4).
If the reading is not 4.000 mA,
select item 2. NO. Repeat steps
and until the ammeter reads
4.000 mA.
EJA:
Fld dev output 4.000
mA equal to reference
meter?
1 Yes
2 No
HELP SET ABORT ENTER
EJA:
Setting fld dev
output to 20mA
DEL SET ABORT OK
7
4
4
5
5
Press OK (F4), and the transmitter
outputs the output signal of 100%.
EJA:
Enter meter value
20.000
HELP DEL ABORT ENTER
8
Carry out the same procedures as
those described under and .
EJA:
Fld dev output 20.000
mA equal to reference
meter?
1 Yes
2 No
HELP ABORT
9
Returning fld dev to original
output appears.
DEL ENTER
(OK)
(ENTER)
(ENTER)
‘1 9.0 5 0‘
EJA:
NOTE-Loop may be
returned to automatic
control
HELP ESC
10
Press OK (F4).
DEL OK
(OK)
(ENTER)
Ammeter reading: 19.050
Ammeter reading: 20.000
Ammeter reading: 4.000
1
F0232.EPS
Select the Scaled D/A trim item.
EJA:
Trim analog output
1 D/A trim
2 Scaled D/A trim
HELP SET HOME OK
EJA:
WARN-Loop should be
removed from
automatic control
DEL SET ABORT OK
2
Press OK (F4).
EJA:
Trim will be scaled
from 4.000 to 20.000
1 Proceed
2 Change
HELP DEL ABORT ENTER
3
Select Change, and press ENTER
(F4).
The same operations as for D/A
trim are required when selecting
item 3. Proceed.
EJA:
Set scale- Lo output
value
4
4
HELP ABORT
4
Enter the value read on the meter
when the signal is 4 mA. In this
case, Enter the value of the voltage
across a 250 resistor (1 V), and
press ENTER (F4).
DEL ENTER
(OK)
(ENTER)
‘1’
EJA:
Set scale- Hi output
value
20
20
HELP ABORT
5
Enter the value read on the meter
when the signal is 20 mA. Then,
enter 5, and press ENTER (F4).
DEL ENTER
(ENTER)
‘5’
Example 2: To adjust using a voltmeter
6
Select Proceed and press ENTER
(F4).
EJA:
Trim will be scaled
from 1.000 to 5.000
1 Proceed
2 Change
HELP SET ABORT ENTER
EJA:
Connect reference
meter
DEL SET ABORT OK
7
Connect the voltmeter, and press
OK (F4).
EJA:
Setting fld dev
output to 4mA
HELP DEL ABORT OK
8
Press OK (F4). The output signal of
0% is output.
(OK)
(OK)
(ENTER)