Appendix A Aggregated Field Diagnostic
Alarms for FOUNDATION Fieldbus
Table Appendix A-1 describes all of the 32 Aggregated Field Diagnostic Alarms used for
Yokogawa products.
Table Appendix A-1 Aggregated Field Diagnostic Alarms (32-bit)
An electric/electronic failure such as amplifier breakdown may have
occurred.
30 F Sensor/Actuator failure A sensor/actuator failure may have occurred.
A device failure may have occurred, or abnormal settings, dirt, poor contact
of wiring and connectors, or poor board installation may have occurred.
28 F (Device specific failure alarm) Device-specific failure
27 F (Device specific failure alarm) Device-specific failure
26 F Backup function in operation
A breakdown has occurred in at least one system of redundant sensors.
The backup sensor is operating normally.
25 - (Reserved) (Reserved)
24 C Firmware update error
A firmware update error has occurred. The operation is being covered by
the existing firmware.
23 C Communication configuration error Communication setting is improper.
Non-routine operations such as initialization, calibration, testing, or
maintenance are in progress.
The device is running with existing settings or abnormal calibration values
because the calibration was performed during an alarm condition.
20 C Device configuration error The settings of sensors or actuators are improper.
19 C Function restricted The device is running partially.
18 C Simulation mode The device is running in the simulation mode.
17 C Manual mode The device is running in the manual mode.
16 C Function Block notice A function block is in the “O/S” or “Unscheduled” state.
(Device specific function check
Device-specific function check alarm
14 - (Reserved) (Reserved)
13 S Sensor/Actuator out of range
The measured value of the sensor or the operating point of the actuator is
out of range.
12 S Out of operating limit The environment or operating condition is out of the specification.
(Device specific out of specification
alarm)
Device-specific out-of-spec alarm
10 - (Reserved) (Reserved)
9 M Temporal decrease of value quality
Although the accuracy satisfies the specification, the measured values are
temporarily unreliable due to degradation.
Deterioration estimated by Time
Based Maintenance
The operation time or the number of operations has exceeded the limit.
Deterioration estimated by Condition
Based Maintenance
The internal algorithm has detected an abnormality.
(Device specific maintenance
request alarm)
Device-specific “maintenance request” alarm
(Device specific maintenance
request alarm)
Device-specific “maintenance request” alarm
4 - (Reserved) (Reserved)
3 C Optional function configuration error
A setting of sub-functions is abnormal although it will not affect the main
measuring functions. Masking this alarm does not affect the operation of
the main functions.
2 - Alarm related information Supplementary information is displayed.
A process alarm has occurred. This alarm may be caused by an
abnormality of devices or peripheral devices.