STRUCTURE DES MENUS
Menu Paramètre Valeurs Etendue
par défaut min. max.
Alarm S1 Setpoint 900.0 mS/cm (high) - inf + inf
Alarm S1 Hysteresis 9.000 mS/cm 0.0 µS/cm + inf
Alarm S1 Delay Time 0.2 sec. 0.0 sec. + inf
Alarm S1 Expire Time 0.0 sec. 0.0 sec. 1800 sec.
Alarm S2 Setpoint 100.0 mS/cm (low) - inf + inf
Alarm S2 Hysteresis 1.000 mS/cm 0.0 µS/cm + inf
Alarm S2 Delay Time 0.2 sec. 0.0 sec. + inf
Alarm S2 Expire Time 0.0 sec. 0.0 sec. 1800 sec.
S1 (control) Expire Time 0.0 sec. 0.0 sec. 1800 sec.
P-control S1 Setpoint 500.0 mS/cm - inf + inf
P-control S1 Range 100.0 mS/cm - inf + inf
P-control S1 Manual Reset 0.000% 0% 100%
PID-control S1 I-time 3600 sec. 1.0 sec. 3600 sec.
PID-control S1 D-time 0.0 sec. 0.0 sec. 60 sec.
S2, S3, S4 semblable à S1