11-14
IM DR232-01E
Set-up data for the SET mode or SETUP mode is read from the internal RAM disk or a floppy
disk.
Loading methods (LOAD MODE in SET mode)
The following two methods are available.
DIRECT
Setup data is loaded immediately after setting has been completed.
TRIGGER 1/TRIGGER 2/TRIGGER 3
The event/action function is used to load set-up data when an event takes place. This function
is useful if you want to record data when an event takes place, with different recording spans.
One event must be set for the LD_TRIG1, LD_TRIG2 and LD_TRIG3 actions during event/
action function setting. For a detailed description of the event/action function, refer to 9.1,
Setting Event/Action Functions (page 9-1).
Confirming the set-up data
To confirm the read set-up data for the SETUP mode, specify SETUP = STORE in the same way
as the SETUP mode setting.
Note
If set-up data saved on another instrument (DR series recorder) is loaded and does not match this
instruments configuration, settings which do not comply with the configuration cannot be made.
No reading is allowed during computing.
The communication function remains disabled during reading.
11.4 Reading Set-up Data