8-12
IM 01R04B04-00E-E 8th edition March 01, 2011 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa

The owmeter is equipped with a CPU error burn-out function used to set the analog output
direction upon
CPU error. When factory-shipment the output of CPU error burn-out is set to HIGH. The setting of the
direction of analog output from burn-out can be changed.
To change the direction of output arising from burn-out, switch the jumper J2 on the CPU Board (see gure
below).
CPU Board
Cable to display
JP2 (Burn out)
High : I ≥ 21.6mA
Low : I ≤ 3.6mA
F810.EPS