9-13
All Rights Reserved. Copyright © 2003, Rota Yokogawa
IM 01R04B04-00E-E 8th edition March 01, 2011 -00
        

Control Drawing No. 8300026
Class I, Division 1; Group A, B, C, D
Class II / III, Division 1, Group E, F, G
AEx d [ia] IIC, Class I, Zone 1, T6
Conduit Seals required within 18 inches.
Use Conductors rated 70°C
TYPE NEMA 4X, IP67
WARNING
WAIT 15 MIN. AFTER POWER-DISCONNECTION
BEFORE OPENING THE ENCLOSURE.

Control Drawing No. 8300027
Class I, Division 1; Group A, B, C,D
AIS Class I / II / III, Division 1, Group A, B, C, D, E, F, G
Class II / III, Division 1, Group E, F, G
AEx d [ia] IIC, Class I, Zone 1, T6
Conduit Seals required within 18 inches.
Use Conductors rated 70°C
TYPE NEMA 4X, IP67
WARNING
WAIT 15 MIN. AFTER POWER-DISCONNECTION
BEFORE OPENING THE ENCLOSURE.

Control Drawing No. 8300028
AIS Class I , Division 1, Group A, B, C, D
AEx [ia] IIC, Class I, Zone 1

Control Drawing No. 8300026
Class I, Division 1; Group A, B, C, D
Class II / III, Division 1, Group E, F, G
AEx d [ia] IIC, Class I, Zone 1, T6
Conduit Seals required within 18 inches.
Use Conductors rated 70°C
TYPE NEMA 4X, IP67
WARNING
WAIT 15 MIN. AFTER POWER-DISCONNECTION
BEFORE OPENING THE ENCLOSURE.
Dual Seal

Control Drawing No. 8300027
IS Class I, Division 1; Group A, B, C, D, T6
Class II / III, Division 1, Group E, F, G
AEx ia IIC, Class I, Zone 0
Use Conductors rated 20°C above max. ambient
temperature
TYPE NEMA 4X, IP67
Temperature Class see Control Drawing

Control Drawing No. 8300026
Class I, Division 1; Group C, D
Class II / III, Division 1, Group E, F, G
AEx d [ia] IIB, Class I, Zone 1, T6
Conduit Seals required within 18 inches.
Use Conductors rated 70°C
TYPE NEMA 4X, IP67
WARNING
WAIT 15 MIN. AFTER POWER-DISCONNECTION
BEFORE OPENING THE ENCLOSURE.

Control Drawing No. 8300027
Class I, Division 1; Group C, D
AIS Class I / II / III, Division 1, Group C, D, E, F, G
Class II / III, Division 1, Group E, F, G
AEx d [ia] IIB, Class I, Zone 1, T6
Conduit Seals required within 18 inches.
Use Conductors rated 70°C
TYPE NEMA 4X, IP67
WARNING
WAIT 15 MIN. AFTER POWER-DISCONNECTION
BEFORE OPENING THE ENCLOSURE.

Control Drawing No. 8300028
AIS Class I , Division 1, Group C, D
AEx [ia] IIB, Class I, Zone 1

Control Drawing No. 8300026
Class I, Division 1; Group C, D
Class II / III, Division 1, Group E, F, G
AEx d [ia] IIB, Class I, Zone 1, T6
Conduit Seals required within 18 inches.
Use Conductors rated 70°C
TYPE NEMA 4X, IP67
WARNING
WAIT 15 MIN. AFTER POWER-DISCONNECTION
BEFORE OPENING THE ENCLOSURE.
Dual Seal

Control Drawing No. 8300027
IS Class I, Division 1; Group A, B, C, D, T6
Class II / III, Division 1, Group E, F, G
AEx ia IIC, Class I, Zone 0
Use Conductors rated 20°C above max. ambient
temperature
TYPE NEMA 4X, IP67
Temperature Class see Control Drawing
Dual Seal