2-32
IM 04L21B01-64EN
Aux
Power
• VT ratio
Specify a value between 1.0 and 6000.0. The decimal place is xed.
• Point
Set the CT ratio’s decimal place to 0, 1, or 2. This number represents the number of
digits after the decimal point.
• CT ratio
The setting range varies depending on the decimal place.
Setting Range Decimal Place
10000 to 32000 0
1000.0 to 9999.9 1
0.05 to 999.99 2
• Low-cut power
Specify a value between 0.05 and 20.00. The decimal place is xed.
Note
Set the VT ratio and CT ratio so that they meet the following condition.
• Secondary rated power × VT ratio × CT ratio < 10 GW.
Phase and Wire System Input Voltage Secondary Rated Power (W)
1P2W 120 100
240 200
1P3W 240 200
3P3W 120 200
240 400