<Toc> <Ind> <3. PC Link Communication >
3-9
IM 77J01J11-01E
3.2.5 BRM Monitoring I Relays on a Bit-by-bit Basis
Function
Reads the ON/OFF statuses of I relays that have been specified in advance by the BRS
command.
Before executing this command, the BRS command must always be executed to
specify which I relays are to be monitored. If no relay has been specified, error code
06 is generated.
For the format of response in the event of failure, see subsection 3.1.2.
The command shown below includes the checksum function. When performing
communication without a checksum, do not include the 2-byte checksum command
element in the command.
Command/Response (for normal operation)
Number of Bytes 12 213 2 11
Command
Element
STX 0 BRM ETX CRAddress
number
(ADDRESS)
CPU
number
01
Checksum
Number of Bytes 12 22111 1 2 11
Response
Element
STX OK d1 d2 d3 ETX CRAddress
number
(ADDRESS)
CPU
number
01
dn Checksum
The response is 0 when the status is OFF or 1 when ON.
dn: registers data of the number of bits specified by the BRS command (n=1 to 32)
dn=0(OFF)
dn=1(ON)
030213E.EPS
Example:
When the burnout and alarms-1 and -2 of the VJ Series signal conditioner with communica-
tion address-1 have been specified to be monitored:
The following command monitors the statuses of burnout (
I0004) and alarm-1 (I0009) and
alarm-2 (
I0010) at communication address-1.
(This command reads the statuses of the I relays specified by the BRS command.)
[Command]
[STX]01010BRMA3[ETX][CR]
With respect to the above command, the ON and OFF statuses of the I relays are returned
as responses.
[Response]
[STX]0101OK000EC[ETX][CR]
All are in OFF statuses.
030214E.EPS
3rd Edition : Oct. 15, 2007-00