<Toc> <Ind> <5. MODBUS Communication >
5-7
IM 77J01J11-01E 3rd Edition : Oct. 15, 2007-00
08 Performs a loop back test.
Function
This function code is used to check the connection for communication.
For the format of responses in the event of failure, see subsection 5.2.2.
The element marked with * is "00" (fixed).
Any value can be selected to send data.
Message (for normal operation)
211None
4221
Number of bytes in RTU mode
Number of bytes in ASCII mode
2
4
Address
Number
(ADDRESS)
Start of
Message Mark
(:)
Element Function
Code (08)
00*
0000
Send Data
(any)
050216E.EPS
Message (continued)
Error
Check
End of Message
Mark (CR+LF)
None2
22
Response (for normal operation)
211None
4221
Number of bytes in RTU mode
Number of bytes in ASCII mode
2
4
Address
Number
(ADDRESS)
Start of
Message Mark
(:)
Element Function
Code (08)
00
0000
Same as
send data
050217E.EPS
Response (continued)
Error
Check
End of Message
Mark (CR+LF)
None2
22
Example:
Sending data "1234h" in hexadecimal to the VJ Series signal conditioner with communica-
tion address 1 to check connection for communication.
The following message sends "1234" (hexadecimal) to communication address 1 in the
ASCII mode.
[Message]
: 010800001234B1[CR][LF]
Start of message mark
When connection for communication is normal, the response whose configuration is the
same as that of the message is returned with respect to the above message.
[Response]
: 010800001234B1[CR][LF]