Yokogawa JUXTA VJ Series Limit Alarms Manual do Utilizador Página 39

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 60
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 38
<Toc> <Ind> <4. Ladder Communication >
4-3
IM 77J01J11-01E
4.2.2 Reading Parameters
Parameters from the PLC are read in the VJ Series signal conditioners in the following
configuration. (The maximum number of data items to be read is 64.)
040204E.EPS
Data of parameter no. (n)
Data of parameter no. (a) Data of parameter no. (b)
Number of Bytes 11 221111
Number of BCD Digits 22 1 4422111
Command Element Address
number
(ADDRESS)
Parameter
number
CPU
number
01
CR
(0D)
LF
(0A)
0 0 00 Number of
read data
(n)
21111
1422111
CR
(0D)
LF
(0A)
5th
digit
0 +/-0 ddddn
Number of Bytes 112
Number of BCD Digits 224
Response Element Address
number
(ADDRESS)
Parameter
number
CPU
number
01
211
14111
5th
digit
0 +/-0 dddd1
211
14111
5th
digit
0 +/-0 dddd2
Example of reading the output value (D register 0008) of the VJ Series
signal conditioner with communication address-1
[Command]
01010008000000010D0A
The output value 500 (BCD code) is returned as a response to the above command (50.0%
is expressed as 500).
[Response]
010100080000005000D0A