<6 OPERATION>
6-29
IM 01R01A11-01EN
(A) Pulse Output (without optional code EM)
1) Wire AXF and CA150 Handy Calibrator or similar as shown in Figure 6.3.9.
2) Select “100 pps” in “Setting Value”. See Figure 6.3.7.
F060307.ai
Figure 6.3.7 “Setting Value” in “Pulse Output”
3) Output
3)-1 When Veri cation Tool is in “online” mode:
Select “Pulse” in “Output Selection” and click “Output”. See Figure 6.3.8
F060308.ai
Figure 6.3.8 “Output Selection” in “Pulse Output”
3)-2 When Veri cation Tool is in “of ine” mode:
3)-2-1 Record the original AXF parameters, and then set them as shown below.
Table 6.3.5 Parameter Settings of “Pulse Output”
HART Parameter
Parameter of
AXF Display
Setting Value
Pulse Scale Device Setup → Easy Setup → Pulse Scale B33/E11 100
Pulse Width Device Setup → Pulse Set → Pulse Width E12 50% Duty
Pulse Unit Device Setup → Easy Setup → Pulse Scale B32/E10 Pulse/s
Test DO (*1) Device Setup → Diag/Service → Output Test→ Test DO N30 Pulse
DO Function(*1)
Device Setup → Con guration → Status Function
→ DO Function
F20 Pulse Output
*1: Only for AXFA14 or AXF Integral Flowmeter
3)-2-2 Output pulse by setting AXF HART parameter “Loop test” to “20 mA”.
Table 6.3.6 Parameter Setting of “Pulse Output”
HART Parameter (DD)
Parameter of
AXF Display
Setting Value
Loop test Device Setup → Diag/Service → Output Test→ Loop test - 20 mA