<Appendix I How to clear VCR (NI-FBUS only)>
App.-57
IM 01R01A01-01E 9th Edition : May 31, 2013-00
Operation Procedure
IncasethatFOUNDATIONeldbusH1communicationsuddenlystops,whichfunctioned
properly on FieldMate before, execute the following operation procedure.
1. Exit FieldMate.
2. Activate/FM/Tool/FMNIFBUSClear.exe
3. Awindowaboveisdisplayed.Check“NumberofConguredVCRs”.Ifthevaluesareclose
to 100, VCR needs to be cleared. Proceed 3. If the valued are small, the other cause of
trouble such as communication card disorder is expected.
4. Select “Clear Stored VCRs” and exit.
5. RestartFieldMateandcheckwhetherFOUNDATIONeldbusH1communicationfunctions
properly.