<ESpecicationsCommontoFieldMateBasicandAdvance>
E-24
IM 01R01A01-01E 9th Edition : May 31, 2013-00
Type B DTM designed by Yokogawa
E030204E.ai
Title bar
Identification area
Application
area
Navigation area
Figure E-3-6
When changing the value of parameters, press “Download to device” button.
YoucanswitchoperationsbetweenOnlineandOfineparameters.
Fromthemenubar,select<Device>,andthenselect<OnlineParameter>or<Ofine
Parameter>.
• Changeofdeviceparameters
Changing the value of parameters requires Block Mode of Function Block of the accessed device
to be O/S mode (Off Service mode) in the most situations.
DTM provides automatic Block Mode change functions as follows.
Function Block to be O/S mode when changing the value of parameters.
Function Block to be recovered when completing the value changes.
Function Block to be O/S mode during download.
The function above is not effective as default. Press “Option button” in the DTM, open Option
window, select it in “Change to “O/S mode, while download” and press “OK”.
Comentários a estes Manuais