Configuring the DX1000/DX2000
Digit of lot number
Select the number of digits of the lot number from 4, 6, or 8. Select [OFF] to disable
the lot number.
Auto increment
ON Automatically sets the lot number of the next measurement to “the lot number of
the current measurement + 1.”
Trend Type
Function for the DX2000 only.
Settings Description
T-Y A trend display with a linear time axis
Circular A trend display with a circular time axis
Partial
Turn Partial [ON] (partially expand) or [OFF] (do not partially expand).
Trend Rate Switching
ON Enables the function that switches the trend interval while the memory sampling
is in progress. The “Second interval [/div]” item is displayed in the setting mode.
When [Trend Rate Switching] is set to [ON], you cannot set [Data Kind] under
[Environment] - [Basic Environment] in the [Basic setting] tab to [E+D].
This setting is fixed at [OFF] if you set [Batch operation qty] to [2] or higher on models
with the multi batch function (/BT2 option; release number 3 or later).
Write Group
Settings Description
Common Write the message to all groups.
Separate Write the message to the displayed group.
Power-Fail Message
ON A message is written when the DX recovers from a power failure while memory
sampling is in progress.
Change Message
ON Writes the time the interval is switched and the new trend interval as a message
when the trend interval is switched.
Scale over
Settings Description
Free The value is set to –over range if the value is less than –30000 and +over
range if the value is greater than 30000 excluding the decimal point. The
value is displayed as –Over and +Over, respectively.
Over The value is set to –over range if the value is less than –5% of the scale and
+over range if the value is greater than 105%. The value is displayed as –
Over and +Over, respectively.
Example:
If the scale is 0.0 to 200.0, the value is set to –over range if the value is less than
–10.0 of the scale and +over range if the value is greater than 210.0.
Note
For computations such as TLOG, CLOG, and report, the handling of the scale over-range value
can be set in advance.
Alarm No Logging
Turn ON when using the Alarm No Logging function. The [Detect] setting is enabled in
the Measure channel/Math channel/Ext channel tab(s).
6.5 Entering Basic Settings