Configuring the CX1000/CX2000
Rate of Change Increase
Select the number of data samples that determines the interval of the rate of change
of an upper limit alarm between [1] and [15].
Rate of Change Decrease
Select the number of data samples that determines the interval of the rate of change
of an lower limit alarm between [1] and [15].
Alarm Hysteresis
Set
the alarm hysteresis to [ON] or [OFF]. When it is [ON], the hysteresis is set to 0.5%
of the scale or the measurement span.
Remote (Option)
You can assign items to be controlled by the eight remote control terminals. This is
possible, if the measurement remote input is available. For details, refer to the CX
User’s Manual (IM 04L31A01-01E or IM 04L31A01-03E).
Select a remote number, and then click the [Copy] button. This copies the setting of that
remote number. When you want to paste the copied setting, select the remote number
where you want to paste the setting, and then click the [Paste] button.
Scan Interval/Memory
Set these parameters when the data type is [EVENT & DISP] or [EVENT].
Click here. (Or choose the [Setting] menu - [SETUP [Basic] Setting] - [Setting].)
Select the channels that
you want to sample.
A/D Integrate
Select from [Auto], [50 Hz], [60 Hz], and [100 ms]. The [Auto] setting automatically
detects the CX power supply frequency, and switches the integration time.
Scan Interval
Select [1s] or [2s].
8.7 Basic Measurement Function Basic Settings