8-34
IM WX104-01E
Select Setpoints
Enter a program pattern for each segment.
Click this tab
Loop number
Start setpoint
(Set in [Default setting])
The target SP of the
previous segment for
subsequent segments
Select Ramp/Soak
Enter target setpoints
Enter the segment duration
Ramp-Rate Time Units
Slope
Segment PID group number
Segment shift action
Wait time
Slope
Wait time
Wait zone number
Ramp/Soak select
Select the type of segment to be specied ([Ramp] or [Soak]).
Target setpoint (ramp segment only)
Set the nal SP of the ramp segment in the range of “EU (0.0% to 100.0%)” (initial
value is 0%) of the measurement span. On Style 3 or later, the value can be set on
the loop whose
Action Loop Set is ON. On Style 2 or earlier, the value can be set on
loops whose [Control Mode] has been set to a mode other than [Off] and [Program
Control] to [On] in [Internal Loop] under the [Setup] tab. During cascade control,
even-numbered loops within the same terminal block cannot be set.
Segment time
Set the segment time in the range of [0:00:01] to [99:59:59] (0 hour 0 min 1 s to 99
hour 59 min 59 s). This item is available at all times during segment time setting
method and only when soak is selected during segment time ramp setting method.
Ramp-rate time unit
Set the ramp-rate time unit for ramps to [Hour] or [Minute]. This item is available only
during segment time setting method.
Ramp
Set the ramp per unit time in the range of “1 digit to EUS (100%) of the measurement
span.” The measurement span and decimal point position of the selectable range
vary depending on the smallest numbered loop to be specied. This item is available
only during ramp in the segment time ramp setting method.
Segment PID group No.
Select the segment PID group number [1] to [8].
This item is not displayed when zone
PID is selected. Only the PID group numbers that can be specied through [Setup]
tab > [Control action] > [PID number] are displayed.
Segment shift action
Set the segment shifting action to [Continue], [Hold] (hold after end of segment),
[Local] (local mode after completing the last segment), or [Reset] (reset mode after
completing the last segment).
Note
When creating the program pattern, data is created so that the segment set to [Local] or [Reset]
is the last segment of program control.
8.6 Program Control Related Setup Operations