8-8
IM WX104-01E
[Burnout/Tuning] Tab
Input Process
Burnout
For the measurement input to each loop, select the burnout direction (open-circuit
detection) from [OFF], [UP], or [DOWN]. The [No.2] setting is valid when [Control
Mode] is set to [PVSwitching], and the [Remote] setting is valid when remote input is
used as measurement input. This setting is invalid for measurement inputs other than
thermocouple and unied signals.
If PV/SP math is OFF, set this in “Control input channel” on page 6-10.
RJC (T
ype, Volt (uV))
This is the reference contact compensation setting for a thermocouple input. Set for
the measurement input of each loop.
The [No.2] setting is valid when [Control Mode]
is set to [PVSwitching], and the [Remote] setting is valid when remote input is used
as measurement input. This setting is invalid for measurement inputs other than
thermocouple and unied signals.
Select from [Internal] and [External] for [T
ype].
When [External] is selected, set [Volt (uV)] between -20000 and 20000 uV
.
If PV/SP math is OFF, set this in “Control input channel” on page 6-10.
Tuning Setting
Switch tuning ON or OFF.
Se
lect [ON] for the parameters that you want to display in the tuning window, and [OFF]
for other parameters.
ID
Select the ID of the item from the following.
SP (target set point), A1 (alarm 1 setting), A2 (alarm 2 setting)
, A3 (alarm 3 setting),
A4 (alarm 4 setting), P (proportional range), I (integration time), D (differentiation
time), OH (upper output limit), OL (lower output limit), MR (manual reset), H (hysteresis),
DR (control action direction), PO (preset output), BS1 (PV1 input bias), FL1 (PV1
input lter), BS2 (PV2 input bias), FL2 (PV2 input lter), RT (ratio setting), RBS (remote
input bias), RFL (remote input lter), or W01 to W36 (control computation constant).
If PV/SP
math is ON, you cannot select BS1, FL1, BS2, FL2, and RFL.
BS1, FL1, BS2, FL2, R, RBS, and RFL are valid on Style 3 or later.
Name
Specify the name of the item using a maximum of 6 characters.
8.3 Control Function Basic Settings