Configuring the CX1000/CX2000
AUX
Remote Setting
When performing measurements by remote, select [Remote]. When [Control Mode]
is set to [Cascade], it is not possible to set [Remote] for secondary measurement loop
numbers. Selection is not possible for the following:
Secondary measurement loop numbers when [Control Mode] is set to [Cascade].
Even-numbered loops when the number of loops is 2, 4, or 6 (
6/4LOOP Select is
set to 4) and [Control Mode] is set to [PVSwitch] (when PV/SP math function is
OFF).
When the number of loops is 6 (6/4LOOP Select is set to 6) and [Control Mode] is
set to [PVSwitch] (when PV/SP math function is OFF).
Alarm Mode
Select from the following whether you want the alarm to be ina
ctive.
ALWA
YS:
Alarm is always active.
STOP:
Alarm inactive when operation is stopped.
STOP/MAN:
Alarm is inactive in manual operation mode or when operation is stopped.
Output Process
When [Control Mode] is set to [Cascade], the output process settings are not
available.
Control Output
Select the type of control output from the following:
Relay
Voltage-pulse
Current-output
On/Off-control relay contact output (not selectable for retransmission loops)
Cycle Time
With a PID proportional to time, set the cycle time (control output cycle) between [1]s
and [1000]s.
Analog-output Type
For the current output, select the output current range from the following:
[4-20mA], [0-20mA], [20-4mA], and [20-0mA].
8.3 Control Function Basic Settings